DC Ground Fault Location                                                       
                                             
                                                   GFAL - A and GFAL-B

                                                          User's Manual                                     By Samco Engineering  

              
          Table of contents
          Sections                                                            

        1.0      Introduction                                                                                                                  
   
        2.0     GFAL- A, Description                                                     

        3.0    GFAL- A, Display meters                                                

        4.0     GFAL- A, Control switches                                             

        5.0    GFAL- A, Field applications                                             

        6.0    GFAL- A, Specifications                                                     

        7.0    GFAL- A, Appendix A,  Battery Pack Maintenance            

        8.0    GFAL- A, Appendix B, Special application
                  Find the value of the fault resistance from each polarity                                  
  
        9.0      GFAL- A, Warranty and Contact Information                        

        10.0    GFAL- B, DC Ground fault tracker unit                         

        11.0    GFAL- B, Applications                                                  

        12.0    GFAL- B, Specifications                                                
   
        13.0    GFAL- B, Appendix C, Battery Pack Maintenance         

        14.0    Appendix D, GFAL-A/B Method
 “Locating DC ground Faults”
                                                         
        15.0    Locating DC ground faults                                              
       
        16.0    Contact and training Information                                      

    1.0 –   Introduction
              Hardware

        The GFAL-A/B method to indicate and locate DC ground faults is made up of two instruments, the GFAL-A (Fig.1)
         is the interrupter unit, also this unit can be use on its own as a DC ground fault analyzer instrument, it connect to the DC
        distribution system with a 3 cable harness.


        The GFAL-B (Fig.2) is the seek out unit, it has a removable sensor that wrap around the conductors for troubleshooting purpose,
        this unit require the GFAL-A to locate DC ground faults.


            Present methodology to indicate DC ground faults

        The existence of a DC ground fault in a multi-feeder DC distribution system is commonly indicated by voltmeters. 
        The voltmeters are attached to the DC distribution system and will indicate ground faults; however, if a second ground fault
        with an equivalent resistance is present on the opposite polarity the voltage equilibrium with respect to ground is restore and
        the voltmeters will fail to indicate the ground faults.


        There are many other variations of this voltage imbalance measurements procedure, a few examples are: the replacement of
        voltmeters with light bulbs, ground fault detector/alarm relays, or a current meter connected at the center point of a voltage divider.


        The major problem with all the cited DC ground fault indication methods is that they use the voltage imbalance technology for
        indication. 

        Consequently, as mentioned earlier, these methods and instruments will have erroneous or no indication at all on multiple ground faults
        if those faults are located on opposite polarity.


        After the DC ground fault it has been detected by the monitor equipment, the fault has to be located in order to correct the problem.

        To find the location of these faults is a very difficult task without having the proper method, instrument and personal training in the art
        of locating DC ground faults.


           The penalty for not locating these faults in a timely manner could include a complete system shutdown costing hundred of thousand
         of dollars per day.

                                   
                     GFAL- A, DC Ground fault Analyzer unit

   
     Samco Engineering  GFAL-A
                                                                          Fig 1
  
    2.0 – GFAL- A, Description

        There are 2 Input Connectors
    1) CHARGER
        Input connector for the 12-18 VDC adapter.
        The Green LED next to the connector will light up when the charging adapter is connected.
        The Red LED BATT LOW will light up when the battery need to be recharge.

    2) PROBE

        Input connector for the positive and negative polarity and site ground of the DC system under test.

    3.0 – GFAL- A, Display meters
        There are 2 display meters  
        1) VOLTS

        The voltmeter displays the AC or DC voltage from the point of connections of the PROBE.
            Remark
        The voltmeter display is in volts e.g. 002 display representing 2 volts disregard the zeros on the left side.

        2) MILLIAMPS
        Display the pseudo fault current from the PROBE point of contact trough the Instrument
            Remark
        The display is in milliamps, 02.0 mA represent 2.0 mA, disregard the zeros on the left side

    4.0 – GFAL- A, Control switches


        FUNCTION SELECT, 6 position switch
                 Remark
         With the FUNCTION SELECT Switch in positions 2-6 the green LED at the upper left corner of the FUNCTION SELECT    
        switch box should light up, (otherwise the internal battery of the Instrument is discharged or disable).

     
        1) OFF  

        In this position, the GFAL-A instrument is turn off. 
            Remark  
        The battery recharge function can be performed (and is recommended) with the FUNCTION SELECT switch in the OFF position

      
        2) AC CONT

        Read the AC voltage from the DC system under test with respect to site ground.
            Remark
        To perform this test, the red (+) cable has to be attached to the system under test.


        3) POS/NEG
        Read the voltage between the Positive Polarity with respect to the Negative Polarity of the DC system under test.

        4) POS/GND
        Read the DC voltage between the Positive Polarity with respect to site ground of the system under test.
            Remark
        Also, enable the POS POLARITY TO GND and the NEG POLARITY TO GND switches.
                                                                                                               
          5) NEG/GND
            Read the DC voltage between the Negative Polarity with respect to site ground of the system under test.
              Remark
        Also, enable the POS POLARITY TO GND and the NEG POLARITY TO GND switches.
   
                                                                                                                                                                                                                                                                                                  6) LOC
        Initiate the interrupter function of the GFAL-A. Also, enable the POS POLARITY TO GND and the
        NEG POLARITY TO GND switches.

        The cycle has two stages, for 6 seconds the ground fault circuit is open and for 6 seconds the ground fault circuit is close.
            Remark
        When the LOC position is selected the blue LED at the upper left corner of the LOC FLASH PULSE wil be on for about 1 second
       
            POS POLARITY TO GND ,  7 position switch
         1 )     OFF
            Disconnect all the pseudo fault resistances from the positive polarity with respect to site ground

       2)     80    
            Insert a 80 Kohm resistor from the positive polarity to ground

       3)     60
            Insert a 60 Kohm resistor from the positive polarity to ground
     
       4)      40  
            Insert a 40 Kohm resistor from the positive polarity to ground

        5)     20
            Insert a 20 Kohm resistor from the positive polarity to ground
       6)     10              
              Insert a 10 Kohm resistor from the positive polarity to ground    
        7)     5   
            Insert a 5 Kohm resistor from the positive polarity to ground  

 
        Remark
        IF the FUNCTION SELECT switch is at position POS/GND or NEG/GND and the POS POLARITY TO GND switch is at any
        position among 2-7, the red LED in the box POS POLARITY TO GND will light up, indicating that a pseudo fault resistance
        from the GFAL-A is connected to the positive polarity of the distribution system with respect to site ground.


        NEG POLARITY TO GND
,  7 position switch
       1)     OFF
            Disconnect all the pseudo fault resistances from the negative polarity with respect to site ground

      2)     80    
            Insert a 80 Kohm resistor from the negative polarity to ground

      3)     60
            Insert a 60 Kohm resistor from the negative
polarity to ground      
      4)      40  
            Insert a 40 Kohm resistor from the negative
polarity to ground
       5)     20
            Insert a 20 Kohm resistor from the  negative polarity to ground
      6)     10              
              Insert a 10 Kohm resistor from the negative polarity to ground    
       7)       5   
            Insert a 5 Kohm resistor from the negative
polarity to ground  
 
        Remark
        IF the FUNCTION SELECT switch is at position POS/GND or NEG/GND and the NEG POLARITY TO GND switch is at any
        position among 2-7, the red LED in the box NEG POLARITY TO GND will light up, indicating that a pseudo fault resistance
        
from the GFAL-A is connected to the negative polarity of the distribution system with respect to site ground.
       
          LOC, 3 position switch        
                  This switch increase (FAST) or decrease (SLOW) momentarily the frequency of the PULSE TRACKER to synchronize the
                GFAL-A with the GFAL-B

                    At the center position the switch is off
               
      5.0 – GFAL- A, Field applications

    Application # 1     AC voltage on DC distribution systems   
      Test
     Directly read AC voltage respect to site ground on DC distribution systems.
      Used for
     Verify the amount of AC Voltage that exists between the DC distribution system with respect to site ground.
     It also will indicate the presence of DC ground fault spikes in the DC distribution systems.
     Caution:    “Phantom” Earth Grounds
     A path to ground through UPS can result in extremely hazardous AC voltages being present between the DC system and the
    grounded racks and switchgear enclosures. 

     This condition in case of person come in direct contact with any conductor of the DC distribution system can result in a
      fatal shot.                                                                                                                                                                          
   
    Application # 2     DC Voltage between polarities
      Test

    Directly read the DC voltage between the positive polarity of a DC distribution system with respect to the negative polarity.

    Used for    
    This test will verify any site voltage indication attached to the DC distribution system.


    Application # 3    Positive voltage respect to site ground.
    Test
    Directly read the DC voltage between the positive polarity with respect to site ground.
    Used for
    This test will verify any site voltmeter(s) attached to the DC distribution system, and there is not crossover contamination
    between two battery independent systems.


    Application # 4     Negative voltage respect to site Gnd.
    Test
    Directly read the DC voltage between the negative polarity respect to site ground.
    Used for
    This test will verify any site voltmeter(s) attached to the DC distribution system, and there is not crossover
    contamination between two battery independent systems.


    Application # 5    DC alarm trip points of operation
    Test
    By introducing a variable resistance between a polarity of a DC system and site ground.
    Used for
    It will test the operation and response of the DC alarm system.
     If the site DC Alarm it is properly working should trip when the introduced resistance is below the set point
    needed to trip the alarm.


    Disconnected, out of commission and out of specifications site DC alarms are quickly exposed by the
    GFAL-A instrument, if the alarm does not respond when the test resistance value is below the trip point
    specify for the alarm.


      Application # 6       Finding the value of fault resistance from each polarity of a battery distribution system
                                   with respect to site ground.

    Test
    By performing two field tests, the second test with the help of a pseudo resistor from the GFAL-A unit connected between
    the DC system with respect to site ground and the use of calculation, the value of the fault resistance from each polarity with
    respect to site ground could be found.

    Used for
    The voltage imbalance readings on DC system are normally performed by voltmeter(s).  The voltmeter(s) data can not give
    information on the actual value of the fault resistance that exists from each polarity respect to site ground. 

    One resistance respect to ground in one polarity cancels the effect (voltage imbalance cancellation) from another resistance
    respect to ground over the other polarity.

     Note
            To know how to perform this method use Appendix B


    Application # 7     Extreme DC system voltages respect to site ground
    Test
    The GFAL-A can determent if the readings of 0.0 VDC from one polarity, and full DC voltage reading from the other polarity,
    with respect to site ground is the result of a short circuit of one of the polarity with respect to ground, an instrument failure
    or is the result of an open connection from the site ground detector unit. 

    Used for
    When a short circuit occurs in a DC distribution system the voltage imbalance readings are: full battery voltage from the polarity
    without the short circuit and near 0.0 VDC from the polarity with the short circuit.

    When one side of a relay on a DC alarm system fails open or a resistor on a voltage divider fails open, the voltage imbalance
    readings are; full battery voltage from the polarity with the open resistance and near 0.0 VDC from the other polarity.

        Remark
    The point is that an open connection and a short circuit to ground will yield the similar voltage readings from the DC system with
    respect to site ground.

    The reliability of a DC System having an open relay or resistor is totally opposite to the reliability of the same system having a short
    circuit from one polarity to ground.


    Application # 8      Predict Maintenance Program
    Test
    Performing periodic readings and creating data base files from both polarities of a DC System.
    Important data to collect are: DC Voltage between polarities and respect to site ground, AC contamination in the DC system,
    DC ground fault resistance from each polarity and DC Alarm system response and operation.

    Used for
    The base line readings from a good working DC system are a very important data to have when grounds fault materialize.

      Application # 9      Miscellaneous Applications         
      Help identify and quantified DC ground faults on DC systems.                   
    Can create balance or imbalance loads respect to site ground on a DC systems up to 6 different values, from 5 K Ohm to 80 K Ohm
     With the help of a DC external power source can analyze de-energize circuits.
    With the help of a decade resistor box can increase the input impedance of the Instrument respect to site ground.
    Useful to train technical people on DC Ground fault theory and troubleshooting.

    6.0 – GFAL- A, Specifications
    Operating DC range                  12 to 270 VDC

    Impedance Range                     5 K to 10 M Ohm (5% accuracy)
    Switching pseudo grounds         By opto-isolation, “Cold Switching”
    Accuracy (full scale)                 Minimum 5%
    Environmental                          30 to 125 Degrees F
    Power source input                  12-18 VDC
    Internal battery life                   24 hr (Rechargeable)
    Display (volts and mA)             2, 3 ½ Digit LCD
     Dimensions                              12” x 7.5” x 11” 
    Weight                                     6 Lb.
    Case (2 colors)                         Gray and yellow
    Warranty                                 1 yr. Parts and Labor


    7.0 – GFAL- A, Appendix A, Battery Pack Maintenance

    The internal battery assembly consists of four (4) Nickel Cadmium (Ni-Cad) cells.
    The voltage of the pack is approximate 5.6 VDC at full charge.
   
    Charging the Pack

     If the red   LED BATT LOW turns on is time to recharge the battery pack.
    A battery charging adapter unit is furnished with the GFAL-A, the adapter has a nominal output voltage of 12-18 VDC and
    a current capacity no less of 500 mA.

    Continuously charging the batteries will not damage the Instrument or the battery pack.
    Also, it is recommended to leave the charging unit a least one-day prior to using the Instrument.
    It is no recommended to use the GFAL-A when the BATT LOW alarm LED is light up, to continue operating the instrument.
     Install the charging unit and when the BATT LOW alarm LED turns off the GFAL-A is ready to be use again.
    If the battery assembly is completely discharged the Instrument has to be charge for a least 2 hr. before can be use.
    The GFAL-A can be used with the charger connected to the main AC line. 
    The GFAL-A should provide 24 hr of continuos operation when the battery pack is full charge.

    Battery pack replacement
   
    Remove only the 10 screws around the edge of the front panel.
    The battery pack is attached to the PCC, remove the tie-wrap and installs a new pack
    It is recommended to leave the charging unit a least one-day prior to using the Instrument.
     If after 2 hr. of charging the Instrument the BATT LOW alarm turns off the GFAL-A can be use with the charging AC adapter
    unit connected to the AC power.


    Battery Specifications

    Voltage at full charge:   5.6 VDC
    Current Capacity:   1600 mA

    CAUTION:

    Replace the battery pack only with Nicad batteries with the same nominal voltage and current capacity to avoid damaging the Instrument.

     8.0 – GFAL- A, Appendix B, Special application

    To find the value of fault resistances from each polarity with respect to site ground on a DC distribution system. 

     Let calculate these fault resistance in a 130 VDC distribution system with a predominant negative ground fault.

    Note: All the voltage readings are in absolute value no signs attach to the readings.

    1) Measuring the voltage of the Positive polarity with respect to site ground:
                                        Vp = 90.0 V

    2) Measuring the voltage of the Negative polarity with respect to site ground:
                                          Vn = 40.0 V

    From the positive polarity of the GFAL-A select a resistor Rfix with respect to ground that will change the distribution system
    positive voltage with respect to ground for no more of 5% to 10% of it original value, assume that this resistor is:

                                          Rfix = 40 K Ohm
    There will be some voltages changes with respect to site ground now.
                                                 
    Voltage from the Positive polarity with respect to ground after the Rfix resistor has been installed
                                        Vpc = 81.0 V
                             
    Voltage from the Negative polarity with respect to ground after the Rfix resistor has been installed
                                        Vnc = 49.0 V

    To calculate the fault resistance from the negative polarity (Rneg)
    
    Rneg = Rfix (Vnc / Vpc - Vn / Vp)
        
    Rneg = 40 K (49.0 / 81.0 - 40.0 / 90.0)
    
    Rneg = 40 K (0.605 - 0.444) = 6.44 Kohm

    To calculate the fault resistance from the positive polarity (Rpos)
    
    Rpos = Rneg ( Vp / Vn ) = 6.44 K ( 90.0 / 40.0) = 14.49 Kohm

    If there is a predominant positive ground fault just apply the same procedure, however install the fix resistor
    Rfix in the negative polarity to do the calculations.


    Note: If some resistance of knowing value still attached to the DC distribution system with respect to site ground,
    by an extra step in the calculation the value of the fault resistances with respect to ground from each polarity can accurately
    be calculated.

    Consult Samco Engineering to obtain these extra steps.


     9.0 – GFAL- A, Warranty and Contact Information

    Samco Engineering warrants this product the GFAL-A to be free from defects in material and workmanship
    for a period of 1 year from the date of shipment.


          LIMITATION OF WARRANTY

    This warranty does not apply to defects resulting from unauthorized modification or misuse of the Instrument. 

    This warranty does not apply to the replacement of the battery unit.

    This warranty is instead of all other warranties, expressed or implied.

     Repairs will be made and the instrument returned with transportation prepaid.

    REMARK
    Samco Engineering shall not be liable for any indirect, special or consequential damages resulting from the use    
    of this instrument.


    Contact Information:

    Samco Engineering
    Fountain Valley, CA 92708
    Phone: (714) 235 - 5901
    E-mail: samcoeng@aol.com
    Web-site: http://www.samcoeng.com
           
                                GFAL- B, DC Ground fault locator unit

    GFAL-B locator unit
                                                        Fig 2
    10.0 – GFAL- B
      Introduction
      The GFAL-A/B method to indicate and locate DC ground faults is made up of two instruments.

       Instrument A
      GFAL-A is the interrupter unit, this unit also can be use as a separate DC ground fault analyzer instrument.

      Instrument B
      The GFAL-B is the “tracker” instrument, this unit require the GFAL-A to operate.

    10.1) Description     Input connectors on the GFAL-B

    CHARGER
      Input connector for the 12-18 VDC battery charger unit.
     The green LED will be on when the charger unit is connected to the GFAL-B.

    SENSOR
     Input connector for the sensor test probe.

    10.2)     Switch
        POWER switch
    In the ON position turn the unit on, in the OFF position turn the unit off.
    With the POWER switch at the OFF position it is OK to re-charge the battery assembly.

    10.3)    Display   
       Alphanumeric display, MILLIAMPS


    For software, battery low and milliamps information.
    The default or maximum mA current that can be display is plus (+) or minus (–) 50.0 mA.

    PULSE TRACKER LED (blue color)

    Will be briefly on (every 12 seconds a part) at the beginner of each tracking pulse cycle and will be off for the
    rest of the cycle.


    CHARGER LED
    The charger LED will be illuminate when the power adapter is connected to the power main.

    11)    GFAL- B, Applications

    The unique application of the GFAL-B instrument is to track with the attached sensor unit the signal produce by
    the GFAL-A throughout the DC distribution system to locate the ground fault.

    If there are one or several ground faults in the range of the instrument specification, it will locate these faults.

    12)    GFAL- B, Specifications

    Operating DC range                 12 to 270 VDC
    Impedance Range                    No load to the DC system
    Environmental                         30 to 125 Degrees F
    Power source input                  12-18 VDC
    Internal battery life                  24 hr (Rechargeable)
    Display                                   LCD Alphanumeric       
    Dimensions                             12” x 7.5” x 11” 
    Weight                                   4 Lb.
    Case    (2 colors)                    Gray and yellow
    Warranty                                1 yr. Parts and Labor

    13) GFAL- B, Appendix C, Battery Pack Maintenance

    The internal battery assembly consists of four (4) Nickel Cadmium (Ni-cad) cells.
    The final voltage of the pack at full charge is approximate 5.6 VDC.

    Charging the Pack

    If the letter “b” (low battery alarm indication) appears in the alphanumeric display, is time to recharge the battery pack.

    A battery charging adapter unit is furnish with the GFAL-B, the adapter has a nominal output voltage of 12 to 18 VDC
    and a current capacity no less of 500 mA


    Continuously charging the batteries will not damage the Instrument or the battery pack.
    The GFAL-B can be used with the charger connected to the main AC line
    Is recommended to leave the charging unit connect to the GFAL-B a least one-day in advance to use the Instrument.
    It is not recommended to use the GFAL-B when the letter “b” is displayed.
    To continue operating the Instrument, install the charging unit and when the “b” alarm disappear, the GFAL-B is ready    
    to be use again.


    If the battery assembly is completely discharged, will be no alphanumeric display, the Instrument has to be charge for
    a least 2 hr. before can be use.

 
    When the battery pack is full charge, the GFAL-B should provide 24 hr of continuos operation.
       
        Battery pack replacement

    Remove only the 4 screws around the edge of the front panel.
    The battery pack is attached to the PCC, remove the tie-wrap and install a new pack
    It is recommended to leave the charging unit a least one-day prior to using the Instrument.

         Battery Specifications
    Voltage at full charge:   5.6 VDC
    Current Capacity:   1600 mA.

    CAUTION
    Replace the battery pack only with Nicad batteries with the same nominal voltage and current capacity to avoid
    damaging the Instrument.



    14.0 – Appendix D, GFAL-A/B Method “Locating DC ground Faults”

    14.1)    Introduction
     The GFAL-A (Fig.1) unit provides the means to analyze the DC distribution system  by introducing
    a fix resistor to site ground and complete an electrical circuit through the site ground fault resistance and the
    battery system (Fig.3).

    Also, makeup synchronization with the detector unit GFAL-B (Fig.2) via the LOC FLASH PULSE switch, and front
    panel FLASH PULSE LED visualization.


        GFAL a b setup
    14.2)    Troubleshooting a DC Distribution System
    To begin troubleshooting a DC DS Install the GFAL-A in a location close to the Battery Room or main DC circuit breaker
    panel.


    CAUTION
    Take all necessary precautions when making connections or working on DC DS energized line or equipment. 

    The operation of the GFAL-A Interrupter will disrupt the Control Room DC ground fault display and or DC alarm system. 
    Always communicate with the control room operator before install and turn on the GFAL-A interrupter.


    Before attach the interrupter to the DC  DS disconnect as possible any instrumentation or electrical apparatus that has
    resistance between the DC 
distribution system and site ground  e.g. voltmeter, DC alarm light bulbs or relays.
    This operation will eliminate unwanted activation of such equipment and will increase the sensitivity and range of the
    troubleshooting procedure.


    A) Set the GFAL-A FUNCTION SELECT switch on the OFF position.
        Connect the PROBE GREEN ground cable to site ground.
        Connect the PROBE RED positive cable to the battery positive polarity.
        Connect the PROBE BLACK negative cable to the battery negative polarity.

    B) Turn the GFAL-A FUNCTION SELECT switch to the AC/CONT position.
        Verify that the AC voltage with respect to the site ground is within the limits established by the site DC DS specifications.
        Normally this reading should be no more than 5.0 VAC in DC DS, however UPS installations without input transformer
        could have a substantial VAC reading.


    C)  Turn the GFAL-A FUNCTION SELECT switch to the POS/NEG position.
         Verify that the positive polarity voltage with respect to the negative polarity voltage is within the limits established by the site
          DC DS specifications.
   
    D) Turn the GFAL-A FUNCTION SELECT switch to the POS/GND position.

         Verify that the positive polarity voltage with respect to site ground is within the limits established by the site DC DS specifications.
         Normally this reading is half of the battery voltage plus or minus 10%.

         If the voltage reading of the positive polarity is bigger for more than 10% of the voltage reading of the negative polarity,
         then the distri-bution system has a predominantly negative fault.

          Remark    
         Using the voltage imbalance as an indication of DC ground fault activity is valid only if the method to calculate the ground fault
         from each polarity is applied first and the value of the fault resistance from each polarity is reveal.

   
        Look at:  Application 8.0 – GFAL-A Appendix B
        To find the value of the fault resistance from each polarity with respect to site ground on a DC distribution system.

    E) Turn the GFAL-A FUNCTION SELECT switch to the NEG/GND position.
        Verify that the negative polarity voltage with respect to site ground is within the limits established by the site
        DC DS specifications.

        Normally this reading is half of the battery voltage plus or minus 10%.

        If the voltage reading of the positive polarity is smaller for more than 10% of the voltage reading of the negative polarity,
        then the distri-bution system has a predominantly positive fault.


        F) How to locate a predominant positive fault

        For a predominant positive fault set the FUNCTION SELECT switch to the NEG/GND position.

        Set the NEG POLARITY TO GND switch to the 80 K-OHM position.
        If the MILLIAMPS display is less than 03.0 mA rotate the NEG POLARITY TO GND switch to 60 K-OHM position
        or less till the reading is more than 03.0 mA.

        It is recommended no to increase the tracing current for more than 10.0 mA.

        14.3)    GFAL- B, Set up
        The Ground Fault Analyzer and Locator GFAL-B (Fig. 2) is a hand held microprocessor based unit, that provide
        a display signal with a Blue LED to help synchronize the GFAL-A, takes the signals from the attach PROBE sensor
        and display fault current measurements in mA.


        A)    Synchronization procedure
        A synchronize visual signal is needed to synchronize the GFAL-A with the GFAL- B.
          The GFAL-A and the GFAL-B repeats a cycle every 12 seconds, where 6 seconds are used for test and 6 seconds are
        used for reference.

          Because there is not hardware connection or a transmitted signal between the two units the synchronization process
        is accomplish by direct operator intervention.  

   
        Turn the POWER switch of the GFAL-B to the ON position.
        When the PULSE TRACKER LED on the GFAL-B turn momentarily on is an indication that the test cycle has begun
        and the reference part of the cycle has ended.  


        After the PULSE TRACKER LED  on the GFAL-B turn on and them off wait for approximate 5 seconds, them rotate
        the FUNCTION SELECT switch on the GFAL-A to the LOC position.


       On the next several cycles of the two units there will be a shift between the FLASH PULSE LED on the GFAL-A and
        the PULSE TRACKER LED on the GFAL-B.


        By activating the GFAL-A PULSE TRACKER switch to the FAST or SLOW position, the cycle on the GFAL-A and
        GFAL-B should be available to synchronize.


        Hint
        If the FLASH PULSE LED on the GFAL-A turn on before the PULSE TRACKER LED in the GFAL-B turn on, move
        the PULSE TRACKER switch to the SLOW position.

        If the FLASH PULSE LED on the GFAL-A turn on after the PULSE TRACKER LED in the GFAL-B turn on, move
        the PULSE TRACKER switch to the FAST position.

        When the two flashing LED’s turn on and off about the same time the two unit are synchronize


       15.0)   Locating DC ground faults
       15.1) Install the GFAL-A as explained in Appendix D
         15.2) Synchronize the 2 units as explained in Appendix D   
       15.3) Connect the magnetic sensor attach to the GFAL-B around the positive and negative cable of a branch of a DC
                distribution system where a search for a ground fault is suspected to exist.

                The main DC breaker panel is the best choice for this initiation task.
                Wait for at least four complete cycles and observe the GFAL-B MILLIAMPS reading.
                If no fault exists in the first branch tested, select another branch until the ground fault has been located.
                If the MILLIAMPS reading on the GFAL-B is continuously more than + or - 3 mA a branch with a ground fault
                has been identify.


        NOTE: It is very possible that more the one branch will have ground fault, in this case adding all the reading from the
        GFAL-B should be near or equal to the reading of the GFAL-A.


        15.4)   At the end of the test
                Disconnect the GFAL-A and reinstall any equipment or apparatus removed before ground fault troubleshooting.      
                Inform the Control Room or supervisor authority immediately after finishing troubleshooting.


        16.0)  Contact Information :

               Samco Engineering                                 
            Fountain Valley, CA 92708
             Phone: (714) 235 - 5901
            E-mail: samcoeng@aol.com
            Web-site: http://www.samcoeng.com                                                                    Return to Home page

               2008